Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2021, 09:24 AM
  • 18 0619_18 0618_06292021_023522.mp4

Date
06/29/2021
W/O
896578
Weather
Dry
Operator/Surveyor
PROPIPE
Sewer ID
Z00692
PipeID
P14469
Time
2:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9059
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_896578_TV18033_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0619
Downstream MH
18 0618
Dir. of Survey
Downstream
Length Surveyed
303.7 ft.
Total Length
303.7 ft.
Structural Index
4
Structural Quick
5G3K
Structural Rating
385
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
385
Pipe schematic from manhole 18 0619 to 18 0618
MH: 18 0619MH: 18 0618downstream0 ft. MGO - General Observation - CONNECTION / DROP CONN. AT THE MH 9 O'CLOCK (UNKNOWN FLOW STATUS)0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06190 ft. MWL - Water Level, 15 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COAT54.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"143.9 ft. TF - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"207.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish279.1 ft. TF - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"303.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish303.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0618303.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
303.7SAP
0MGOCONNECTION / DROP CONN. AT THE MH 9 O'CLOCK (UNKNOWN FLOW STATUS)
303.7AMH18 0618
279.1TF
303.7MGOCONNECTION AT THE MH 9 OC'LOCK
2.6SAP
207.1SRV
143.9TF
54.4TFA
2.6SRV
0MWM
0AMH18 0619
0MWL
2.6MGOMAG COAT

Properties (7)

additional_info
630074062821202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-06-29T02:24:57-07:00
documentation
PROPIPE
is_lateral_inspection
false