Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2021, 05:10 AM
  • 05 1487_05 1486_06162021_222204.mp4

Date
06/16/2021
W/O
896355
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06713
Time
10:10 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8986
Sewer Name
05 EL NIDO TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_896355_TV05300_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
24 in.
Upstream MH
05 1486
Downstream MH
05 1487
Dir. of Survey
Upstream
Length Surveyed
294.7 ft.
Total Length
294.7 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
126
Pipe schematic from manhole 05 1486 to 05 1487
MH: 05 1486MH: 05 1487upstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 14872.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish79.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN292.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start292.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start292.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start292.7 ft. MGO - General Observation - 55% MAG COAT294.6 ft. MWM - Water Mark, 25 %of cross sectional area294.7 ft. MWL - Water Level, 20 %of cross sectional area294.7 ft. AMH - Downstream Manhole, Survey Begins - 05 1486294.7 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/ACTIVE

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
215.3TFC
0MWL
292DAGS
294.7SSS
55.5TFOPEN
0AMH05 1486
0.1MWM
294.7SAV
294.7AMH05 1487
2DAGS
2MGO55% MAG COAT
2.1SSS
2.1SAV
0MGOCONN @ MH 10 O'CLOCK/ACTIVE

Properties (7)

additional_info
630074061621201
custom_field_three
AGGREGATE VISIBLE/SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2021-06-16T22:10:51-07:00
documentation
PROPIPE
is_lateral_inspection
false