Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 16, 2021, 07:05 AM
  • 05 2341_05 1483_06162021_000925.mp4

Date
06/16/2021
W/O
896355
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06709
Time
12:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8945
Sewer Name
05 EL NIDO TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_896355_TV05300_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
21 in.
Upstream MH
05 1483
Downstream MH
05 2341
Dir. of Survey
Upstream
Length Surveyed
23.1 ft.
Total Length
23.1 ft.
Structural Index
3
Structural Quick
3424
Structural Rating
20
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole 05 1483 to 05 2341
MH: 05 1483MH: 05 2341upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 23410 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONN @ MH 12 O'CLOCK/ACTIVE0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish20.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.1 ft. MGO - General Observation - 45% MAG COAT21.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.1 ft. MWL - Water Level, 5 %of cross sectional area23.1 ft. AMH - Downstream Manhole, Survey Begins - 05 148323.1 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2.3SSS
0MWL
23.1AMH05 2341
0AMH05 1483
23.1SAV
2MGO45% MAG COAT
0MWM
2.3SAV
23.1MGOCONN @ MH 12 O'CLOCK/ACTIVE
2DAGS
23.1SSS
21DAGS

Properties (7)

additional_info
630074061521202
custom_field_three
AGGREGATE VISIBLE/SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2021-06-16T00:05:40-07:00
documentation
PROPIPE
is_lateral_inspection
false