Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 04:46 AM
  • 08 0171_08 0170_06232021_215836.mp4

Date
06/23/2021
W/O
896214
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00009
PipeID
P00228
Time
9:46 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9003
Sewer Name
08 GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_896214_TV08166_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
08 0171
Downstream MH
08 0170
Dir. of Survey
Downstream
Length Surveyed
330.3 ft.
Total Length
330.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
316
Pipe schematic from manhole 08 0171 to 08 0170
MH: 08 0171MH: 08 0170downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 01710 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"194.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"288.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"296.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"328.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish328.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0170

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMH08 0171
0MWL
194.9TFA
137.8TFA
328.1DAGS
288.3TBA
245.9TF
0MWM
90.5TFC
328.1CM
330.3AMH08 0170
296.9TFC
40TFA
18.1CM
2DAGS

Properties (7)

additional_info
630069062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T21:46:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false