Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2021, 08:26 AM
  • 01 0267_01 0266B_06142021_013017.mp4

Date
06/14/2021
W/O
896354
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01315
Time
1:26 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8897
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_896354_TV01204_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0267
Downstream MH
01 0266B
Dir. of Survey
Downstream
Length Surveyed
62.2 ft.
Total Length
62.2 ft.
Structural Index
3
Structural Quick
4A3A
Structural Rating
104
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
3
Overall Quick
Overall Rating
128
Pipe schematic from manhole 01 0267 to 01 0266B
MH: 01 0267MH: 01 0266Bdownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 01 02670 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start59.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish60 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish62.2 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE62.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0266B

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
62.2MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWM
0MWL
59.2FM
60SSS
0MGOCONN @ MH 9 O'CLOCK/CAPPED
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SSS
60DAGS
60CM
62.2AMH01 0266B
0AMH01 0267
2CM
2FM
0MGOROACHES @ MH
2DAGS

Properties (7)

additional_info
630074061421001
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-06-14T01:26:04-07:00
documentation
PROPIPE
is_lateral_inspection
false