Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2021, 08:39 AM
  • 01 0266A_01 0266_06142021_014522.mp4

Date
06/14/2021
W/O
896354
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01313
Time
1:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8897
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_896354_TV01204_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0266A
Downstream MH
01 0266
Dir. of Survey
Downstream
Length Surveyed
118.6 ft.
Total Length
118.6 ft.
Structural Index
3
Structural Quick
4D3D
Structural Rating
207
O&M Index
2
O&M Quick
2D00
O&M Rating
46
Overall Index
3
Overall Quick
Overall Rating
253
Pipe schematic from manhole 01 0266A to 01 0266
MH: 01 0266AMH: 01 0266downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 0266A0 ft. MGO - General Observation - VERMIN @ MH 9 O'CLOCK (1) RAT0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"116 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish116 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish116 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish118.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish118.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE118.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0266

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
118.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH01 0266A
2CM
2.4FM
61.3TFC
0MGOVERMIN @ MH 9 O'CLOCK (1) RAT
118.5FM
28.3TF
2DAGS
0MWL
0MWM
116CM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
116DAGS
118.6AMH01 0266
116SSS
2SSS

Properties (7)

additional_info
630074061421001
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-06-14T01:39:15-07:00
documentation
PROPIPE
is_lateral_inspection
false