Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2021, 10:22 AM
  • 01 0235_01 0234A_06152021_032650.mp4

Date
06/15/2021
W/O
896354
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01280
Time
3:22 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8899
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_896354_TV01204_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
12 in.
Upstream MH
01 0235
Downstream MH
01 0234A
Dir. of Survey
Downstream
Length Surveyed
139.7 ft.
Total Length
139.7 ft.
Structural Index
3
Structural Quick
3A00
Structural Rating
33
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
87
Pipe schematic from manhole 01 0235 to 01 0234A
MH: 01 0235MH: 01 0234Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02350 ft. MWL - Water Level, 20 %of cross sectional area2 ft. LFW - Lining Failure Wrinkled, from 12 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. MGO - General Observation - PIPE IS LINED137 ft. LFW - Lining Failure Wrinkled, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish137 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish139.7 ft. MGO - General Observation - FOOTAGE WRONG ON DATABASE139.7 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE139.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0234A139.7 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN

Observations (12)

DistanceCodeObservation
0MWM
0AMH01 0235
137LFW
0MWL
2LFW
139.7MGOFOOTAGE WRONG ON DATABASE
139.7MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
6.4MGOPIPE IS LINED
139.7AMH01 0234A
137DAGS
139.7MGOCONN @ MH 3 O'CLOCK/OPEN

Properties (6)

custom_field_three
RFIR NO SEVRE DEFECTS/ PIPE IS LINED
custom_field_two
4
customer
1
datetime
2021-06-15T03:22:06-07:00
documentation
PROPIPE
is_lateral_inspection
false