Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2021, 10:27 AM
  • 01 0233A_01 0233_06152021_033431.mp4

Date
06/15/2021
W/O
896354
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01277
Time
3:27 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8899
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_896354_TV01204_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
12 in.
Upstream MH
01 0233A
Downstream MH
01 0233
Dir. of Survey
Downstream
Length Surveyed
306.8 ft.
Total Length
306.8 ft.
Structural Index
2
Structural Quick
312K
Structural Rating
123
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
243
Pipe schematic from manhole 01 0233A to 01 0233
MH: 01 0233AMH: 01 0233downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0233A2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.1 ft. MGO - General Observation - PIPE IS LINED209.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN304 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish304 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish306.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0233

Observations (11)

DistanceCodeObservation
0MWL
304DAGS
0MGOCONN @ MH 9 O'CLOCK/
4.1MGOPIPE IS LINED
2SSS
304SSS
0MWM
209.8TFOPEN
306.8AMH01 0233
2DAGS
0AMH01 0233A

Properties (7)

additional_info
630074061421202
custom_field_three
RFIR NO SEVRE DEFECTS/ PIPE IS LINED
custom_field_two
4
customer
1
datetime
2021-06-15T03:27:55-07:00
documentation
PROPIPE
is_lateral_inspection
false