Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2021, 07:58 AM
  • 02 0950_02 0949_06152021_010949.mp4

Date
06/15/2021
W/O
896122
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00279
PipeID
P03519
Time
12:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8938
Sewer Name
02 MONTEBELLO TRUNK
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_896122_TV02320_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
27 in.
Upstream MH
02 0949
Downstream MH
02 0950
Dir. of Survey
Upstream
Length Surveyed
332.4 ft.
Total Length
332.4 ft.
Structural Index
2
Structural Quick
322L
Structural Rating
138
O&M Index
2
O&M Quick
412L
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
274
Pipe schematic from manhole 02 0949 to 02 0950
MH: 02 0949MH: 02 0950upstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Ends - 02 09500 ft. MGO - General Observation - ROACHES @ MH2.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start330.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start330.4 ft. MGO - General Observation - 75% MAG COAT330.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start332.4 ft. MGO - General Observation - ROACHES @ MH332.4 ft. MWL - Water Level, 35 %of cross sectional area332.4 ft. AMH - Downstream Manhole, Survey Begins - 02 0949332.4 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • General Observation - 75% MAG COAT

    2 ft. - General Observation - 75% MAG COAT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    332.4 ft. - General Observation - ROACHES @ MH

Observations (14)

DistanceCodeObservation
2SSS
330DAGS
332.4MGOCONN @ MH 3 O'CLOCK/OPEN
332.4AMH02 0950
332.4MGOROACHES @ MH
330.3SAP
0MGOROACHES @ MH
2MGO75% MAG COAT
3.7SAP
330SSS
0MWL
0AMH02 0949
0MWM
2DAGS

Properties (7)

additional_info
630069061421201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-06-15T00:58:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false