Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2021, 06:22 AM
  • 18 0681_18 0680_06022021_234820.mp4

Date
06/02/2021
W/O
890827
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00706
PipeID
P14530
Time
11:22 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8935
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_890827_TV18104_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0681
Downstream MH
18 0680
Dir. of Survey
Downstream
Length Surveyed
603.5 ft.
Total Length
603.5 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
357
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
357
Pipe schematic from manhole 18 0681 to 18 0680
MH: 18 0681MH: 18 0680downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06810 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start338.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"599.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish599.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE603.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0680

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0.4 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    599.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0.4MGOCOCKROACHES IN MANHOLE
603.5AMH18 0680
599.4SAP
599.5MGOCOCKROACHES IN MANHOLE
0AMH18 0681
0MWM
0MWL
2MGOMAG COATING THROUGHOUT
2SAP
338.9TFA

Properties (7)

additional_info
630069060221201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-06-02T23:22:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false