Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2021, 07:44 AM
  • 18 0694_18 0863_06022021_005623.mp4

Date
06/02/2021
W/O
890827
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14544
Time
12:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8884
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_890827_TV18104_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0694
Downstream MH
18 0863
Dir. of Survey
Downstream
Length Surveyed
304.6 ft.
Total Length
304.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0694 to 18 0863
MH: 18 0694MH: 18 0863downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06940 ft. MWL - Water Level, 20 %of cross sectional area0.2 ft. MWM - Water Mark, 25 %of cross sectional area2.4 ft. MGO - General Observation - MAG COAT2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start304.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0863304.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK304.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH18 0694
0MWL
304.6AMH18 0863
2.6SAV
304.6MGOCONNECTION AT MH 3 O'CLOCK
2.4MGOMAG COAT
304.6SAV
0.2MWM

Properties (7)

additional_info
630138060121201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-06-02T00:44:13-07:00
documentation
PROPIPE
is_lateral_inspection
false