Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2021, 09:36 AM
  • 18 0732_18 0731_05262021_025428.mp4

Date
05/26/2021
W/O
890827
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14585
Time
2:36 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8880
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_890827_TV18104_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0732
Downstream MH
18 0731
Dir. of Survey
Downstream
Length Surveyed
14.5 ft.
Total Length
14.5 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0732 to 18 0731
MH: 18 0732MH: 18 0731downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 07320 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK14.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish14.5 ft. AMH - Downstream Manhole, Survey Ends - 18 073114.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    14.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0AMH18 0732
14.5MGOCONNECTION AT MH 3 O'CLOCK
0MWM
2.1SAP
0.1MGOCONNECTION AT MH 6 O'CLOCK
0MWL
14.5SAP
14.5AMH18 0731
14.5SRV

Properties (7)

additional_info
630138052521202
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-05-26T02:36:37-07:00
documentation
PROPIPE
is_lateral_inspection
false