Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2021, 04:43 AM
  • 18 1182_18 0719_05252021_215445.mp4

Date
05/25/2021
W/O
890827
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14572
Time
9:43 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8880
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_890827_TV18104_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
18 1182
Downstream MH
18 0719
Dir. of Survey
Downstream
Length Surveyed
249.1 ft.
Total Length
249.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 1182 to 18 0719
MH: 18 1182MH: 18 0719downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11820 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start249.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0719

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0AMH18 1182
0MWM
249.1SAV
249.1AMH18 0719
0MWL
2.1MGOMAG COAT
2.1SAV

Properties (7)

additional_info
630138052521202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-25T21:43:08-07:00
documentation
PROPIPE
is_lateral_inspection
false