Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2021, 11:18 AM
  • C 0217_C 0216A_772021_042415.mp4

Date
07/07/2021
W/O
0896123
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09612
Time
4:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1865
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20210707MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0217
Downstream MH
C 0216A
Dir. of Survey
Downstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole C 0217 to C 0216A
MH: C 0217MH: C 0216Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - 98% MAG COAT START26.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE104 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active154.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active163.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open168.6 ft. MGO - General Observation - 98% MAG COAT265.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active265.1 ft. MGO - General Observation - MAG COAT 98% FINISH265.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING EELING CONCRETE UNDER MAG COAT265.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active265.6 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - 98% MAG COAT START

    2 ft. - General Observation - 98% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    26.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Observation - 98% MAG COAT

    168.6 ft. - General Observation - 98% MAG COAT

Observations (15)

DistanceCodeObservation
265.1MGOConn. @ Mh, 3 O' Clock. Active
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
26.6SSSBLISTERING PEELING CONCRETE
0MWM
0AMH4:20AM
0MWL
265.1MGOMAG COAT 98% FINISH
168.6MGO98% MAG COAT
154.1TFAActive
265.1SSSBLISTERING EELING CONCRETE UNDER MAG COAT
265.1MGOConn. @ Mh, 9 O' Clock. Active
265.6AMH4:45AM
163.1TFOpen
2MGO98% MAG COAT START
104TFAActive

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE-98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2021-07-07T04:18:09-07:00
documentation
MARTIN,REVELES,OLIVER 111,BARR
is_lateral_inspection