Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2021, 09:21 AM
  • C 0219_C 0217_772021_032036.mp4

Date
07/07/2021
W/O
0896123
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09613
Time
2:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1865
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20210707MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0219
Downstream MH
C 0217
Dir. of Survey
Downstream
Length Surveyed
406.7 ft.
Total Length
406.7 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole C 0219 to C 0217
MH: C 0219MH: C 0217downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:15AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active LARGE OUTGOING0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT85% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG12.2 ft. MGO - General Observation - ABANDONED VCP CAPPED MH47.5 ft. MGO - General Observation - 95% MAG COAT START111.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open139 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE170.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG276.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active406.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC406.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE406.1 ft. MGO - General Observation - 95% MAG COAT FINISH406.7 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT85% START

    2 ft. - General Observation - MAG COAT85% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - ABANDONED VCP CAPPED MH

    12.2 ft. - General Observation - ABANDONED VCP CAPPED MH

  • General Observation - 95% MAG COAT START

    47.5 ft. - General Observation - 95% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    139 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    170.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (17)

DistanceCodeObservation
0AMH3:15AM
406.7AMH4:00AM
2SSSBLISTERING PEELING CONCRETE
2MGOMAG COAT85% START
0MWL
170.7SRVSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Active LARGE OUTGOING
276.4TFActive
0MWM
406.1SAMSEVERE AGG SPORATIC
406.1SSSBLISTERING PEELING CONCRETE
139SSSBLISTERING PEELING CONCRETE
406.1MGO95% MAG COAT FINISH
12.2MGOABANDONED VCP CAPPED MH
47.5MGO95% MAG COAT START
2SAMSEVERE AGG
111.7TFOpen

Properties (6)

custom_field_three
SEVERE AGG MISSING-95% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2021-07-07T02:21:35-07:00
documentation
MARTIN,REVELES,OLIVER 111,BARR
is_lateral_inspection
false