- Date
- 07/07/2021
- W/O
- 0896123
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00124
- PipeID
- P09613
- Time
- 2:21 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1865
- Sewer Name
- C JOINT OUTFALL C - UNIT 3E
- City
- LONG BEACH
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 03
- Page No.
- 14
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210707MDM_JOINT_OUTFALL_C_UNIT_3E
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- C 0219
- Downstream MH
- C 0217
- Dir. of Survey
- Downstream
- Length Surveyed
- 406.7 ft.
- Total Length
- 406.7 ft.
- Structural Index
- 3
- Structural Quick
- 5141
- Structural Rating
- 13
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 13
Pipe schematic from manhole C 0219 to C 0217 Observation photos (7)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - General Observation - MAG COAT85% START

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

12.2 ft. - General Observation - ABANDONED VCP CAPPED MH

47.5 ft. - General Observation - 95% MAG COAT START

139 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

170.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG