Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 09:54 AM
  • 18 0271_18 0270_06232021_030645.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14099
Time
2:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9053
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0270
Downstream MH
18 0271
Dir. of Survey
Upstream
Length Surveyed
429.8 ft.
Total Length
429.8 ft.
Structural Index
2
Structural Quick
322P
Structural Rating
176
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
2
Overall Quick
Overall Rating
346
Pipe schematic from manhole 18 0270 to 18 0271
MH: 18 0270MH: 18 0271upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 02710 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/0.8 ft. MGO - General Observation - 1 (RAT) @ MH2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish427.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start427.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start427.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start429.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN429.8 ft. MWM - Water Mark, 25 %of cross sectional area429.8 ft. MWL - Water Level, 20 %of cross sectional area429.8 ft. AMH - Downstream Manhole, Survey Begins - 18 0270

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
429.8AMH18 0271
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
427DAGS
427SSS
2CM
0MWM
2SSS
429.8CM
0MWL
429MGO1 (RAT) @ MH
2DAGS
0AMH18 0270
429.8MGOCONN @ MH 3 O'CLOCK/

Properties (7)

additional_info
630074062221203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T02:54:21-07:00
documentation
PROPIPE
is_lateral_inspection
false