Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 10:13 AM
  • 18 0269_18 0268_06232021_032459.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14097
Time
3:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9053
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0269
Downstream MH
18 0268
Dir. of Survey
Downstream
Length Surveyed
332.8 ft.
Total Length
332.8 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
332
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
464
Pipe schematic from manhole 18 0269 to 18 0268
MH: 18 0269MH: 18 0268downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02690 ft. MWL - Water Level, 15 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES330 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish332 ft. MGO - General Observation - ROACHES @ MH332.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN332.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0268

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
330SSS
330DAGS
332.6CM
0MWM
332.6MGOCONN @ MH 3 O'CLOCK/OPEN
0AMH18 0269
2CM
332MGOROACHES @ MH
0MWL
332.8AMH18 0268
3.1CL
2SSS
2DAGS

Properties (7)

additional_info
630074062221203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T03:13:44-07:00
documentation
PROPIPE
is_lateral_inspection
false