Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 10:37 AM
  • 18 0267A_18 0267_06232021_034238.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14096
Time
3:37 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9053
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0267A
Downstream MH
18 0267
Dir. of Survey
Downstream
Length Surveyed
140.3 ft.
Total Length
140.3 ft.
Structural Index
3
Structural Quick
5241
Structural Rating
152
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
206
Pipe schematic from manhole 18 0267A to 18 0267
MH: 18 0267AMH: 18 0267downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 0267A0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES5 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish138 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish138 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish140 ft. MGO - General Observation - ROACHES @ MH140.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish140.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0267

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    2.3 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
140.3CM
140MGOROACHES @ MH
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2DAGS
5B
0AMH18 0267A
2SSS
138SSS
0MWM
2CM
2B
0MWL
140.3AMH18 0267
2.3FM
138DAGS

Properties (7)

additional_info
630074062221203
custom_field_three
BROKEN PIPE/MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-06-23T03:37:10-07:00
documentation
PROPIPE
is_lateral_inspection
false