Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 06:50 AM
  • 18 0263_18 0262_06232021_235628.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14091
Time
11:50 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0263
Downstream MH
18 0262
Dir. of Survey
Downstream
Length Surveyed
100.1 ft.
Total Length
100.1 ft.
Structural Index
2
Structural Quick
382C
Structural Rating
64
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole 18 0263 to 18 0262
MH: 18 0263MH: 18 0262downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02632 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES98 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish98 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish100 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE100 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish100.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0262

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    50.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
2SSS
100.1AMH18 0262
98DAGS
98SSS
0MWM
2DAGS
100MGOCONN @ MH 9 O'CLOCK/ACTIVE
2CM
0MWL
100CM
0AMH18 0263
50.2CL

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T23:50:51-07:00
documentation
PROPIPE
is_lateral_inspection
false