Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 06:57 AM
  • 18 0262_18 0261_06242021_000622.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14090
Time
11:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0262
Downstream MH
18 0261
Dir. of Survey
Downstream
Length Surveyed
240 ft.
Total Length
240 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
235
O&M Index
2
O&M Quick
2H12
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
331
Pipe schematic from manhole 18 0262 to 18 0261
MH: 18 0262MH: 18 0261downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02620 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start6.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.7 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES111.5 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES238 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish240 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish240 ft. AMH - Downstream Manhole, Survey Ends - 18 0261240 ft. MGO - General Observation - ROACHES @ MH240 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    4.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    89.7 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
111.5RFJ
240DAGS
0MWM
238SSS
240AMH18 0261
0MWL
2SSS
240MGOROACHES @ MH
4.2DAGS
0AMH18 0262
89.7RFJ
240CM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
6.7CM

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T23:57:09-07:00
documentation
PROPIPE
is_lateral_inspection
false