Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 07:48 AM
  • 18 0258_18 0257_06242021_005633.mp4

Date
06/24/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14086
Time
12:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0258
Downstream MH
18 0257
Dir. of Survey
Downstream
Length Surveyed
182.9 ft.
Total Length
182.9 ft.
Structural Index
2
Structural Quick
3F2F
Structural Rating
177
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
249
Pipe schematic from manhole 18 0258 to 18 0257
MH: 18 0258MH: 18 0257downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 02580 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"131.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"180 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish182.8 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE182.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish182.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0257182.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
182.9AMH18 0257
0AMH18 0258
0MWL
0MWM
180SSS
2SSS
182.8MGOCONN @ MH 3 O'CLOCK/ACTIVE
182.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
180DAGS
182.8CM
2DAGS
131.4TFC
55.2TFC
5.6CM

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T00:48:56-07:00
documentation
PROPIPE
is_lateral_inspection
false