Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 04:45 AM
  • 18 0255_18 0254_06232021_215654.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14083
Time
9:45 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0255
Downstream MH
18 0254
Dir. of Survey
Downstream
Length Surveyed
257.1 ft.
Total Length
257.1 ft.
Structural Index
2
Structural Quick
3I2I
Structural Rating
248
O&M Index
2
O&M Quick
2I00
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
350
Pipe schematic from manhole 18 0255 to 18 0254
MH: 18 0255MH: 18 0254downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ ACTIVE0 ft. MGO - General Observation - CONN @ MH 9 OCLOCK/ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02552 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES16.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"153.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"229.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"255 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish257.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE257.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish257.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE257.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0254

Observation photos (2)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    12.6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MWL
0MGOCONN @ MH 3 O'CLOCK/ ACTIVE
257.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
229.9TFC
255SSS
77.9TFC
0MGOCONN @ MH 9 OCLOCK/ACTIVE
257.1CM
12.6CL
257.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
2SSS
2DAGS
255DAGS
257.1AMH18 0254
153.6TFC
16.8CM
0AMH18 0255

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T21:45:46-07:00
documentation
PROPIPE
is_lateral_inspection
false