Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 04:57 AM
  • 18 0254_18 0253_06232021_220017.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14082
Time
9:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0254
Downstream MH
18 0253
Dir. of Survey
Downstream
Length Surveyed
38.7 ft.
Total Length
38.7 ft.
Structural Index
3
Structural Quick
3722
Structural Rating
25
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
39
Pipe schematic from manhole 18 0254 to 18 0253
MH: 18 0254MH: 18 0253downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 02540 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish36 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish38.6 ft. MGO - General Observation - ROACHES @ MH38.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish38.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0253

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
36DAGS
38.6MGOROACHES @ MH
0AMH18 0254
0MWL
38.7CM
2SSS
38.7AMH18 0253
2DAGS
0MWM
36SSS
4.2CM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T21:57:16-07:00
documentation
PROPIPE
is_lateral_inspection
false