Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 05:03 AM
  • 18 0253_18 0252_06232021_221138.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14081
Time
10:03 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0253
Downstream MH
18 0252
Dir. of Survey
Downstream
Length Surveyed
214.8 ft.
Total Length
214.8 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
210
O&M Index
2
O&M Quick
2G1A
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
306
Pipe schematic from manhole 18 0253 to 18 0252
MH: 18 0253MH: 18 0252downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02532 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"81.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"153.1 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start158 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"212 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish212 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish214.6 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish214.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish214.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0252214.8 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE214.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    153.1 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
153.1RFJ
2SSS
9.3TFC
212SSS
214.6RFJ
2DAGS
0MWM
158TFC
0MWL
214.8AMH18 0252
81.3TFC
214.8MGOCONN @ MH 3 O'CLOCK/ACTIVE
212DAGS
0AMH18 0253
214.8MGOCONN @ MH 9 O'CLOCK/ACTIVE
5.2CM
214.7CM

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T22:03:22-07:00
documentation
PROPIPE
is_lateral_inspection
false