Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 05:24 AM
  • 18 0250_18 0219_06232021_223511.mp4

Date
06/23/2021
W/O
896153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14078
Time
10:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9054
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_896153_TV18003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0250
Downstream MH
18 0219
Dir. of Survey
Downstream
Length Surveyed
314 ft.
Total Length
314 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
310
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
314
Pipe schematic from manhole 18 0250 to 18 0219
MH: 18 0250MH: 18 0219downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02500 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN144.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN219.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"312 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish312 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish314 ft. AMH - Downstream Manhole, Survey Ends - 18 0219314 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish314 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
144.7TFOPEN
314AMH18 0219
0MWL
2DAGS
3CM
312DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
314CM
219.8TFA
314MGOCONN @ MH 3 O'CLOCK/ACTIVE
67.5TFOPEN
312SSS
2SSS
0AMH18 0250
0MGOCONN @ MH 3 O'CLOCK/ ACTIVE

Properties (7)

additional_info
630074062321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-23T22:24:16-07:00
documentation
PROPIPE
is_lateral_inspection
false