Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 10:26 AM
  • 18 0268_18 0267A_06232021_033444.mp4

Date
06/23/2021
W/O
896581
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P22249
Time
3:26 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9052
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_896581_TV18186_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0268
Downstream MH
18 0267A
Dir. of Survey
Downstream
Length Surveyed
198.6 ft.
Total Length
198.6 ft.
Structural Index
3
Structural Quick
413G
Structural Rating
118
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
120
Pipe schematic from manhole 18 0268 to 18 0267A
MH: 18 0268MH: 18 0267Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02687.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start188 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE188 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES192.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES198.6 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 3 OCLOCK198.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish198.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0267A

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    188 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    192.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWM
188TFACTIVE
198.6MGOACTIVE CONNECTION AT THE MH 3 OCLOCK
198.6CM
188DAGS
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
198.6AMH18 0267A
7.5CM
0AMH18 0268
192.3FM

Properties (7)

additional_info
630074062221202
custom_field_three
MULTIPLE CRACKS/FRACTURE
custom_field_two
3
customer
1
datetime
2021-06-23T03:26:26-07:00
documentation
PROPIPE
is_lateral_inspection
false