Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 05:11 AM
  • 15 0671_15 0670_06222021_223947.mp4

Date
06/22/2021
W/O
896249
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12563
Time
10:11 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8991
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_896249_TV15005_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0671
Downstream MH
15 0670
Dir. of Survey
Downstream
Length Surveyed
179.1 ft.
Total Length
179.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0671 to 15 0670
MH: 15 0671MH: 15 0670downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06710 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"93 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"100.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"137.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"155.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"167 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"176.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish176.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish179.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK179.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0670

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    12.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    30.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
167TFC
137.1TFC
100.8TFC
12.3CM
176.8SSS
40.6TFC
0AMH15 0671
179.1MGOCONNECTION AT MH 3 O'CLOCK
2.1SAV
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
93TF
30.8SSS
176.8SAV
155.2TFC
0MWL
179.1AMH15 0670

Properties (6)

custom_field_three
CRACKS, AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-06-22T22:11:18-07:00
documentation
PRO PIPE
is_lateral_inspection
false