Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 06:42 AM
  • 15 0666_15 0665_06232021_000036.mp4

Date
06/22/2021
W/O
896249
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12558
Time
11:42 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8991
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_896249_TV15005_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0666
Downstream MH
15 0665
Dir. of Survey
Downstream
Length Surveyed
295.8 ft.
Total Length
295.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0666 to 15 0665
MH: 15 0666MH: 15 0665downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 06662.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"166.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"175.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"201.5 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES224.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"226.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"241.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"293.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0665

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    201.5 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    224.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

Observations (17)

DistanceCodeObservation
2.2SAV
5.1SSS
295.8AMH15 0665
226.6TFC
224.4TB
0MWM
175.6TF
241.7TF
201.5CS
0MGOCONNECTION AT MH 9 O'CLOCK
70.3TF
0MWL
293.5SSS
0MGOCONNECTION AT MH 3 O'CLOCK
293.5SAV
0AMH15 0666
166.6TF

Properties (6)

custom_field_three
CRACKS, AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-06-22T23:42:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false