Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 08:54 AM
  • 15 0661_15 0660_06232021_020954.mp4

Date
06/23/2021
W/O
896249
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12553
Time
1:54 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8991
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_896249_TV15005_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0661
Downstream MH
15 0660
Dir. of Survey
Downstream
Length Surveyed
378.9 ft.
Total Length
378.9 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 0661 to 15 0660
MH: 15 0661MH: 15 0660downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06610 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MWM - Water Mark, 50 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"213.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"288.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"297.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"376.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish378.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED378.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0660

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    213.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (15)

DistanceCodeObservation
376.3SSS
0MWL
0AMH15 0661
297.1TFC
378.9MGOCONNECTION AT MH 3 O'CLOCK CAPPED
213.2TB
51.2TFC
147TF
15.5SSS
2.6SAV
376.3SAV
288.3TF
378.9AMH15 0660
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWM

Properties (6)

custom_field_three
CRACKS, AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-06-23T01:54:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false