Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2021, 09:10 AM
  • 15 0660_B 0621_06232021_022844.mp4

Date
06/23/2021
W/O
896249
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12552
Time
2:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8991
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_896249_TV15005_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0660
Downstream MH
B 0621
Dir. of Survey
Downstream
Length Surveyed
412.3 ft.
Total Length
412.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0660 to B 0621
MH: 15 0660MH: B 0621downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06600 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"105.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"149.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"218 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"279.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"411.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish411.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish412.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK412.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK412.3 ft. AMH - Downstream Manhole, Survey Ends - B 0621

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    149.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    218 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

Observations (16)

DistanceCodeObservation
411.9SAV
0MWL
279.7TF
412.1MGOCONNECTION AT MH 9 O'CLOCK
11.4SSS
412.3AMHB 0621
149.4TB
97TF
218TB
412.1MGOCONNECTION AT MH 3 O'CLOCK
411.9SSS
105.8TFC
0AMH15 0660
0MWM
2.5SAV
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED

Properties (6)

custom_field_three
AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-06-23T02:10:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false