Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 04:52 AM
  • 18 1118_18 1117_06242021_221034.mp4

Date
06/24/2021
W/O
896154
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00711
PipeID
P14970
Time
9:52 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9055
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_896154_TV18058_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 1118
Downstream MH
18 1117
Dir. of Survey
Downstream
Length Surveyed
300.7 ft.
Total Length
300.7 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
179
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
179
Pipe schematic from manhole 18 1118 to 18 1117
MH: 18 1118MH: 18 1117downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11180 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES13.8 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES14.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"16.8 ft. FS - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES22.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES26.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start64.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES114.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300.7 ft. AMH - Downstream Manhole, Survey Ends - 18 1117

Observation photos (5)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    2.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    13.8 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    16.8 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    76.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
22.9CL
0AMH18 1118
269.3TFC
300.7CM
219.2TFC
166.8TFC
0MWM
26.7CM
16.8FS
13.8CM
300.7AMH18 1117
14.9TFC
114.7TFC
2.1CL
64.3TFC
76.3FM
0MWL

Properties (7)

additional_info
630074062421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T21:52:20-07:00
documentation
PROPIPE
is_lateral_inspection
false