Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 05:12 AM
  • 18 1117_18 1116A_06242021_222731.mp4

Date
06/24/2021
W/O
896154
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00711
PipeID
P14969
Time
10:12 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9055
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_896154_TV18058_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 1117
Downstream MH
18 1116A
Dir. of Survey
Downstream
Length Surveyed
83.4 ft.
Total Length
83.4 ft.
Structural Index
3
Structural Quick
3B21
Structural Rating
47
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
47
Pipe schematic from manhole 18 1117 to 18 1116A
MH: 18 1117MH: 18 1116Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11170 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area4.7 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES10.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"28.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish83.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK83.4 ft. AMH - Downstream Manhole, Survey Ends - 18 1116A

Observation photos (3)

  • Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES

    4.7 ft. - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    28.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
4.7FC
15TFC
0AMH18 1117
83.4CM
64.6TFC
10.7CM
83.4MGOCONNECTION AT THE MH 3 OC'LOCK
83.4AMH18 1116A
28.6TB
0MWM
0MWL

Properties (7)

additional_info
630074062421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T22:12:53-07:00
documentation
PROPIPE
is_lateral_inspection
false