Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 05:29 AM
  • 18 1116A_18 1116_06242021_223304.mp4

Date
06/24/2021
W/O
896154
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00711
PipeID
P14968
Time
10:29 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9055
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_896154_TV18058_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 1116A
Downstream MH
18 1116
Dir. of Survey
Downstream
Length Surveyed
54.8 ft.
Total Length
54.8 ft.
Structural Index
3
Structural Quick
3A00
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 18 1116A to 18 1116
MH: 18 1116AMH: 18 1116downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 1116A0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"30.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.8 ft. AMH - Downstream Manhole, Survey Ends - 18 111654.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    11.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
54.8CM
0AMH18 1116A
2.3CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
54.8AMH18 1116
30.6TFC
11.8TB
0MWL
54.8MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM

Properties (7)

additional_info
630074062421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T22:29:02-07:00
documentation
PROPIPE
is_lateral_inspection
false