Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 05:33 AM
  • 18 1116_18 1115_06242021_224112.mp4

Date
06/24/2021
W/O
896154
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00711
PipeID
P14967
Time
10:33 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9055
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_896154_TV18058_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 1116
Downstream MH
18 1115
Dir. of Survey
Downstream
Length Surveyed
161.6 ft.
Total Length
161.6 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
93
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
3
Overall Quick
Overall Rating
155
Pipe schematic from manhole 18 1116 to 18 1115
MH: 18 1116MH: 18 1115downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 11160 ft. MGO - General Observation - GREASE IN MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - GREASE DEPOSITS5.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - GREASE DEPOSITS161.6 ft. AMH - Downstream Manhole, Survey Ends - 18 1115161.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
4DAGSGREASE DEPOSITS
126.6TFC
0MWM
0AMH18 1116
0MGOGREASE IN MH
28.1TFC
159.5DAGSGREASE DEPOSITS
161.6AMH18 1115
0MWL
161.6CM
5.3CM
77.8TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK

Properties (7)

additional_info
630074062421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T22:33:34-07:00
documentation
PROPIPE
is_lateral_inspection
false