Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 05:41 AM
  • 18 1115_18 1114_06242021_225508.mp4

Date
06/24/2021
W/O
896154
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00711
PipeID
P14966
Time
10:41 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9055
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_896154_TV18058_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 1115
Downstream MH
18 1114
Dir. of Survey
Downstream
Length Surveyed
326.3 ft.
Total Length
326.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 18 1115 to 18 1114
MH: 18 1115MH: 18 1114downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11150 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"220.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.3 ft. AMH - Downstream Manhole, Survey Ends - 18 1114326.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    113.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    127.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    202.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (16)

DistanceCodeObservation
0AMH18 1115
318.9TFC
69.7TFC
4.2CM
119.2TFC
326.3AMH18 1114
113.3TB
127.9TB
202.9TB
0MWM
171.4TFC
220.4TFC
0MWL
17.9TFC
326.3CM
269.9TFC

Properties (7)

additional_info
630074062421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-24T22:41:40-07:00
documentation
PROPIPE
is_lateral_inspection
false