Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2021, 08:23 AM
  • 01 1226_01 1225_6262021_012811.mp4

Date
06/26/2021
W/O
0890879
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00217
PipeID
P02050
Time
1:23 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1856
Sewer Name
01 SANTA FE AVENUE TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
202106025MDM_SANTA_FE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 1226
Downstream MH
01 1225
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
2
Structural Quick
322A
Structural Rating
30
O&M Index
3
O&M Quick
4237
O&M Rating
31
Overall Index
3
Overall Quick
Overall Rating
61
Pipe schematic from manhole 01 1226 to 01 1225
MH: 01 1226MH: 01 1225downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE5 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SLIGHT6.7 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE10 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H12.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H12.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL14.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL17.3 ft. MWM - Water Mark, 50 %of cross sectional area17.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL17.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H20 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT WITH PIPE CHIPPING22.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS22.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS22.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS22.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS42.8 ft. SZ - Surface Other, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON51.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open92.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open166.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open170.1 ft. SZ - Surface Other, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON171.6 ft. RMJ - Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR, Start179.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-60% ROOTS183.3 ft. RMJ - Roots Medium Joint, from 02 to 07 o'clock, 25 %, within 8 inches of joint: YESR188.1 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 20 %, within 8 inches of joint: YESR190.7 ft. RMJ - Roots Medium Joint, from 03 to 06 o'clock, 25 %, within 8 inches of joint: YESR203.6 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR209 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR218.9 ft. RMJ - Roots Medium Joint, from 03 to 06 o'clock, 20 %, within 8 inches of joint: YESR221.7 ft. RMJ - Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR, Finish242 ft. MWM - Water Mark, 30 %of cross sectional area253.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open266.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open333.9 ft. MWM - Water Mark, 50 %of cross sectional area349.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% HAIRLINE AT JOINTS349.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS349.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS349.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS AT JOINTS349.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING OUTER SUFACE349.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active349.5 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. Capped349.8 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE

  • Water Mark, 50 %of cross sectional area

    17.3 ft. - Water Mark, 50 %of cross sectional area

  • Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT WITH PIPE CHIPPING

    20 ft. - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT WITH PIPE CHIPPING

  • Surface Other, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON

    42.8 ft. - Surface Other, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON

  • Surface Other, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON

    170.1 ft. - Surface Other, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE VCP CORRISON

  • Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR, Start

    171.6 ft. - Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Roots Medium Joint, from 02 to 07 o'clock, 25 %, within 8 inches of joint: YESR

    183.3 ft. - Roots Medium Joint, from 02 to 07 o'clock, 25 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 06 o'clock, 25 %, within 8 inches of joint: YESR

    190.7 ft. - Roots Medium Joint, from 03 to 06 o'clock, 25 %, within 8 inches of joint: YESR

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open

    266.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open

Observations (44)

DistanceCodeObservation
188.1RMJ
349.5FC40% HAIRLINE AT JOINTS
166.5TFOpen
221.7RMJ
170.1SZPOSSIBLE VCP CORRISON
203.6RMJ
10FCH
22.7FCHAIRLINE AT JOINTS
17.3MWM
349.5FL10% SLIGHT AT JOINTS
2SSSBLISTERING OUTER SURFACE
12.2FCH
242MWM
349.5FL10% HAIRLINE AT JOINTS
14.5FCSL
0MWM
209RMJ
22.7FLHAIRLINE AT JOINTS
333.9MWM
179.5TFDOpen-60% ROOTS
6.7FCHAIRLINE
22.7FLSLIGHT AT JOINTS
349.5FC40% SLIGHT AT JOINTS AT JOINTS
17.3FCSL
171.6RMJ
17.3FCH
349.8AMH2:30AM
183.3RMJ
218.9RMJ
190.7RMJ
253.4TFOpen
349.5SSSBLISTERING OUTER SUFACE
349.5MGOConn. @ Mh, 9 O' Clock. Active
92.7TFOpen
12.2FCSL
0AMH1:30AM
266.1TFOpen
22.7FCSLIGHT AT JOINTS
5FCSLIGHT
349.5MGOConn. @ Mh, 12 O' Clock. Capped
0MWL
42.8SZPOSSIBLE VCP CORRISON
51.4TFOpen
20FCSLIGHT WITH PIPE CHIPPING

Properties (6)

custom_field_three
SLIGHT FRACTURES -POSSIBLE VCP CORRISON
custom_field_two
2
customer
LACSD
datetime
2021-06-26T01:23:37-07:00
documentation
MARTIN,OLIVER 111,BARR
is_lateral_inspection
false