Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 07:29 AM
  • 01 1230_01 1229_6252021_005410.mp4

Date
06/25/2021
W/O
0890879
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00217
PipeID
P02054
Time
12:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1855
Sewer Name
01 SANTA FE AVENUE TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
202106025MDM_SANTA_FE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 1230
Downstream MH
01 1229
Dir. of Survey
Downstream
Length Surveyed
190.8 ft.
Total Length
190.8 ft.
Structural Index
2
Structural Quick
4835
Structural Rating
145
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
145
Pipe schematic from manhole 01 1230 to 01 1229
MH: 01 1230MH: 01 1229downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE 2 FEET2 ft. MMC - Material Change, Concrete pipe (non-reinfored) - 2 FEET2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 2 FEET4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT BLISTERING OUTER SURFACE12.2 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE14.9 ft. MGP - General Photograph - 15" VCP14.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H17.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE17.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H22.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H25.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H40.7 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SLIGHT42.8 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL45.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H48.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H50.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H53.7 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - H55.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL58.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT60.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H63.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H63.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL66.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL68.3 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - SL70.7 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL73.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL76 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL79.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL81 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL83.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL86.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL88.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H91 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL95.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL98.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL103.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H103.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL111.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H111.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H113.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL116.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL118.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL126.4 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SDL128.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H128.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL134.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL134.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H138.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL141.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H144.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H146.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H149.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT151.6 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: NO - SL156.7 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - SL159.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL162.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL164.3 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - H171.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL171.5 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - H176.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H176.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL179.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H182 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL184.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL187.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL190.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING OUTER LAYER190.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active190.8 ft. AMH - Downstream Manhole, Survey Ends - 1:45AM

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE 2 FEET

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE 2 FEET

  • Material Change, Concrete pipe (non-reinfored) - 2 FEET

    2 ft. - Material Change, Concrete pipe (non-reinfored) - 2 FEET

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 2 FEET

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 2 FEET

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT BLISTERING OUTER SURFACE

    4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT BLISTERING OUTER SURFACE

  • General Photograph - 15" VCP

    14.9 ft. - General Photograph - 15" VCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE

    17.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    58.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    66.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    176.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL

    176.8 ft. - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL

Observations (72)

DistanceCodeObservation
171.5FCSL
128.4FCH
2SSSPEELING CONCRETE 2 FEET
184.4FCSL
76FCSL
111.1FCH
81FCSL
12.2FCHAIRLINE
113.6FMSL
149.7FMSLIGHT
42.8FCSL
126.4FCSDL
2MMC2 FEET
98.4FCSL
134.1FLSL
118.9FCSL
50.2FCH
103.4FCH
190.1SSSBLISTERING OUTER LAYER
17.5SSSBLISTERING OUTER SURFACE
63.6FCH
128.4FCSL
17.5FLH
111.1FLH
138.9FCSL
176.1FLH
0MGOConn. @ Mh, 9 O' Clock. Active
151.6FCSL
48.1FCH
162.4FMSL
146.5FCH
2SAMSEVERE AGG 2 FEET
134.1FCH
141.8FCH
182FCSL
0MWL
179.5FLH
68.3FCSL
53.7FCH
159.3FMSL
14.9MGP15" VCP
40.7FCSLIGHT
79.3FMSL
45.3FCH
55.4FCSL
116.1FCSL
176.8FCSL
190.8AMH1:45AM
70.7FCSL
60.6FCH
73.3FCSL
86.3FCSL
187.4FCSL
83.4FCSL
25.1FCH
88.3FCH
66.1FMSL
14.9FCH
22.7FLH
91FCSL
164.3FCH
0AMH12:45AM
4SSSSLIGHT BLISTERING OUTER SURFACE
103.4FCSL
156.7FCSL
171.5FCH
58.1FMSLIGHT
0MWM
63.6FCSL
144.1FCH
95.7FCSL
190.1MGOConn. @ Mh, 9 O' Clock. Active

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
2
customer
LACSD
datetime
2021-06-25T00:29:06-07:00
documentation
MARTIN,REVELES,OLIVER 111,RAMERIZ
is_lateral_inspection
false