- Date
- 06/03/2021
- W/O
- 891214
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00941
- PipeID
- P11076
- Time
- 11:08 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8978
- Sewer Name
- H JOINT OUTFALL H - UNIT 9B
- City
- PICO RIVERA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 03
- Purpose
- Routine Assessment
- Project
- RFIR_WO_891214_TV18175_MAY2021
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 25 in.
- Width
- 25 in.
- Upstream MH
- H 0669
- Downstream MH
- H 0668
- Dir. of Survey
- Downstream
- Length Surveyed
- 382.5 ft.
- Total Length
- 382.5 ft.
- Structural Index
- 3
- Structural Quick
- 3N2N
- Structural Rating
- 380
- O&M Index
- 2
- O&M Quick
- 412H
- O&M Rating
- 94
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 474
Pipe schematic from manhole H 0669 to H 0668 Observation photos (5)

3.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

3.6 ft. - General Observation - MAG COATING THROUGHOUT

3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

26.8 ft. - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

344.5 ft. - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start