Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2021, 05:32 PM
  • H 0686_H 0685_06022021_105320.mp4

Date
06/02/2021
W/O
891214
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00941
PipeID
P11093
Time
10:32 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8976
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_891214_TV18175_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0686
Downstream MH
H 0685
Dir. of Survey
Downstream
Length Surveyed
782.3 ft.
Total Length
782.3 ft.
Structural Index
3
Structural Quick
3^2^
Structural Rating
780
O&M Index
2
O&M Quick
412^
O&M Rating
316
Overall Index
2
Overall Quick
Overall Rating
1096
Pipe schematic from manhole H 0686 to H 0685
MH: H 0686MH: H 0685downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06862 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 80% MAG COAT780 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish782.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish782.3 ft. AMH - Downstream Manhole, Survey Ends - H 0685782.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 80% MAG COAT

    2 ft. - General Observation - 80% MAG COAT

Observations (11)

DistanceCodeObservation
2SSS
782.3SAV
780DAGS
2DAGS
782.3AMHH 0685
0MWM
2SAV
0MWL
2MGO80% MAG COAT
782.3SSS
0AMHH 0686

Properties (6)

custom_field_three
AGGREGATE VISIBLE.SPALLING
custom_field_two
3
customer
1
datetime
2021-06-02T10:32:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false