Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2021, 04:25 PM
  • 15 0259_15 0258_05262021_101644.mp4

Date
05/26/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12182
Time
9:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8969
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0258
Downstream MH
15 0259
Dir. of Survey
Upstream
Length Surveyed
343.4 ft.
Total Length
343.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 15 0258 to 15 0259
MH: 15 0258MH: 15 0259upstream0 ft. MSA - Survey Abandoned - UNABLE TO GET PAST0 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Finish - UNDERFLOW0 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish20.5 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"83.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish124.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"221.6 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"319.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"333.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start333.4 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW341.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start343.4 ft. AMH - Downstream Manhole, Survey Begins - 15 0258343.4 ft. MWM - Water Mark, 25 %of cross sectional area343.4 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (8)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

    10 ft. - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    24 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    121.8 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    218.5 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    322.9 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Survey Abandoned - UNABLE TO GET PAST

    343.4 ft. - Survey Abandoned - UNABLE TO GET PAST

Observations (14)

DistanceCodeObservation
259.6SSS
0AMH15 0258
121.8TBC
10SAV
322.9TBC
218.5TBC
343.4MSAUNABLE TO GET PAST
10OBZUNDER FLOW
343.4OBZUNDERFLOW
2SSS
0MWM
24TBC
343.4SAV
0MWL

Properties (6)

custom_field_three
AGGEGATE VISBLE
custom_field_two
3
customer
1
datetime
2021-05-26T09:25:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false