Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2021, 04:53 PM
  • 15 0241_15 0240_05282021_102330.mp4

Date
05/28/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12163
Time
9:53 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8970
Sewer Name
15 SAN JOSE CREEK TRUNK
City
HACIENDA HEIGHTS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0240
Downstream MH
15 0241
Dir. of Survey
Upstream
Length Surveyed
749.3 ft.
Total Length
749.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0240 to 15 0241
MH: 15 0240MH: 15 0241upstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 15 02410 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"348.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"542.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"592.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start747.3 ft. MGO - General Observation - MAG COAT747.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start749.3 ft. MWL - Water Level, 20 %of cross sectional area749.3 ft. MWM - Water Mark, 35 %of cross sectional area749.3 ft. AMH - Downstream Manhole, Survey Begins - 15 0240

Observation photos (5)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    157.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    400.4 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    552.3 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

Observations (12)

DistanceCodeObservation
552.3TB
0MWL
749.3SAP
0MWM
0AMH15 0240
400.4TB
2MGOMAG COAT
157.2SSS
749.3AMH15 0241
749.3SSS
2SAP
207TB

Properties (6)

custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2021-05-28T09:53:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false