Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2021, 05:27 PM
  • 15 0258_15 0257A_05262021_104116.mp4

Date
05/26/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12181
Time
10:27 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8969
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0258
Downstream MH
15 0257A
Dir. of Survey
Downstream
Length Surveyed
384.9 ft.
Total Length
384.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0258 to 15 0257A
MH: 15 0258MH: 15 0257Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02580 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW100.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"198 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"302.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"350.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"384.9 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Finish - UNDER FLOW384.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish384.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK384.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0257A

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

    10.6 ft. - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    100.9 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    198 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    302.5 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    350.3 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

Observations (13)

DistanceCodeObservation
0AMH15 0258
2SAV
384.9OBZUNDER FLOW
0MWL
302.5TBC
384.9SAV
384.9MGOCONNECTION AT MH 3 O'CLOCK
0MWM
100.9TBC
10.6OBZUNDER FLOW
198TBC
350.3TBC
384.9AMH15 0257A

Properties (6)

custom_field_three
AGGEGATE VISBLE
custom_field_two
3
customer
1
datetime
2021-05-26T10:27:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false