Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2021, 10:52 AM
  • 15 0254_15 0253_05182021_040427.mp4

Date
05/18/2021
W/O
890822
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00627
PipeID
P12176
Time
3:52 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8915
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0254
Downstream MH
15 0253
Dir. of Survey
Downstream
Length Surveyed
269.1 ft.
Total Length
269.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
413I
O&M Rating
254
Overall Index
2
Overall Quick
Overall Rating
254
Pipe schematic from manhole 15 0254 to 15 0253
MH: 15 0254MH: 15 0253downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02542 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start25.6 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS43.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish266.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish269.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0253269.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - COCKROACHES IN MANHOLE

    269.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
25.6DSZDEBRIS
2DAGS
266.5DAGS
0MGOCOCKROACHES IN MANHOLE
0MGOCONNECTION AT MH 3 O'CLOCK
0MWM
269.1AMH15 0253
0MWL
124.4TFC
220.9TFC
0AMH15 0254
269.1MGOCOCKROACHES IN MANHOLE
266.5DSZ
43.2TFC

Properties (7)

additional_info
630069051721201
custom_field_three
SETTLED DEPOSITS/DEBRIS
custom_field_two
3
customer
1
datetime
2021-05-18T03:52:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false