Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2021, 06:48 PM
  • 15 0246_15 0245_05282021_130058.mp4

Date
05/28/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12168
Time
11:48 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8970
Sewer Name
15 SAN JOSE CREEK TRUNK
City
HACIENDA HEIGHTS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0245
Downstream MH
15 0246
Dir. of Survey
Upstream
Length Surveyed
866.9 ft.
Total Length
866.9 ft.
Structural Index
3
Structural Quick
3b2b
Structural Rating
865
O&M Index
2
O&M Quick
2`00
O&M Rating
330
Overall Index
2
Overall Quick
Overall Rating
1195
Pipe schematic from manhole 15 0245 to 15 0246
MH: 15 0245MH: 15 0246upstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Ends - 15 02460 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Finish - UNDER FLOW0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish216.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"411.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 8"638.3 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"642.6 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"804.4 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW817.8 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"817.8 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"823.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"855.9 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 8"864.9 ft. MGO - General Observation - MAG COAT864.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start864.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start866.9 ft. MWM - Water Mark, 25 %of cross sectional area866.9 ft. AMH - Downstream Manhole, Survey Begins - 15 0245866.9 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (10)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    43.8 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"

    49.1 ft. - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"

    49.1 ft. - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"

  • Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

    62.5 ft. - Obstacles Other, 10 %of cross sectional area, at 06 o'clock, Start - UNDER FLOW

  • Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"

    224.3 ft. - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"

    228.6 ft. - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    650 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

Observations (20)

DistanceCodeObservation
62.5OBZUNDER FLOW
2MGOMAG COAT
866.9SSS
866.9MGOCONNECTION AT MH 12 O'CLOCK CAPPED
0MWM
11TBA
2SSS
0AMH15 0245
455.8TF
650TB
43.8TBA
866.9AMH15 0246
0MWL
49.1TBC
228.6TBC
2SAV
866.9OBZUNDER FLOW
49.1TBC
224.3TBC
866.9SAV

Properties (6)

custom_field_three
AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-05-28T11:48:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false