Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2021, 03:38 PM
  • 15 0244_15 0243_06012021_085309.mp4

Date
06/01/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12166
Time
8:38 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8974
Sewer Name
15 SAN JOSE CREEK TRUNK
City
HACIENDA HEIGHTS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0244
Downstream MH
15 0243
Dir. of Survey
Downstream
Length Surveyed
516.8 ft.
Total Length
516.8 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
515
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
515
Pipe schematic from manhole 15 0244 to 15 0243
MH: 15 0244MH: 15 0243downstream0 ft. MGO - General Observation - CONNECTION 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 02440 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.8 ft. MGO - General Observation - MAG COAT2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start516.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish516.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish516.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0243

Observation photos (3)

  • General Observation - MAG COAT

    2.8 ft. - General Observation - MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.8MGOMAG COAT
2.8SAV
0MGOCONNECTION 9 OCLOCK
0AMH15 0244
0MWL
0MWM
516.8SSS
2.8SSS
516.8SAV
516.8AMH15 0243

Properties (6)

custom_field_three
SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-06-01T08:38:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false