Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2021, 05:24 PM
  • 15 0242_15 0241_05282021_105019.mp4

Date
05/28/2021
W/O
890822
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00627
PipeID
P12164
Time
10:24 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8970
Sewer Name
15 SAN JOSE CREEK TRUNK
City
HACIENDA HEIGHTS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_890822_TV15001_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0241
Downstream MH
15 0242
Dir. of Survey
Upstream
Length Surveyed
496.7 ft.
Total Length
496.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 0241 to 15 0242
MH: 15 0241MH: 15 0242upstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 15 02420 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"384.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"494.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start494.3 ft. MGO - General Observation - MAG COAT494.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start496.7 ft. MWM - Water Mark, 25 %of cross sectional area496.7 ft. AMH - Downstream Manhole, Survey Begins - 15 0241496.7 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.4 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    112.1 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    399.8 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

Observations (11)

DistanceCodeObservation
2.4SAV
399.8TBC
2.4MGOMAG COAT
0MWM
496.7SSS
496.7AMH15 0242
112.1TBC
496.7SAV
2.4SSS
0AMH15 0241
0MWL

Properties (6)

custom_field_three
AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2021-05-28T10:24:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false