Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2021, 06:38 AM
  • 22 0611_22 0610_05122021_002829.mp4

Date
05/11/2021
W/O
891211
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00827
PipeID
P16958
Time
11:38 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8850
Sewer Name
22 SUNFLOWER TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_891211_TV22166_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0611
Downstream MH
22 0610
Dir. of Survey
Downstream
Length Surveyed
455.7 ft.
Total Length
455.7 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
450
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
450
Pipe schematic from manhole 22 0611 to 22 0610
MH: 22 0611MH: 22 0610downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 06110 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 25 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.3 ft. MGO - General Observation - 45% MAG COAT39.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"43.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"84.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"88.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"117 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"141.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 8" - OPEN169.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"193.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"222.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"243.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 8"263.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 8"271.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"316.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"341.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"356.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"365.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"393.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 8" - OPEN418.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"452.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish453 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish455.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0610455.7 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 45% MAG COAT

    20.3 ft. - General Observation - 45% MAG COAT

Observations (29)

DistanceCodeObservation
117TFC
455.7AMH22 0610
2.1SSS
452.5SSS
141.3TFOPEN
84.2TFC
0MWM
263.3TFA
316.4TFC
418.2TFC
43.2TFC
20.3MGO45% MAG COAT
2.1SAP
169.8TFC
356.9TFC
271.6TFA
243.3TFC
453SAP
39.2TFC
365.2TFC
455.7MGOCONN @ MH 9 O'CLOCK/ACTIVE
193.9TFC
341.5TFC
0AMH22 0611
88.4TFC
393.5TFOPEN
0MGOROACHES @ MH
0MWL
222.8TFC

Properties (6)

custom_field_three
AGGREGATE VISIBLE, SPALLING
custom_field_two
2
customer
1
datetime
2021-05-11T23:38:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false