- Date
- 05/07/2021
- W/O
- 891211
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00827
- PipeID
- P16968
- Time
- 2:08 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8903
- Sewer Name
- 22 SUNFLOWER TRUNK
- City
- COVINA
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- RFIR_WO_891211_TV22166_MAY2021
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 22 0620
- Downstream MH
- 22 0619
- Dir. of Survey
- Downstream
- Length Surveyed
- 459.4 ft.
- Total Length
- 459.4 ft.
- Structural Index
- 3
- Structural Quick
- 3Q2Q
- Structural Rating
- 455
- O&M Index
- 2
- O&M Quick
- 2Q00
- O&M Rating
- 182
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 637
Pipe schematic from manhole 22 0620 to 22 0619 Observation photos (5)

0 ft. - General Observation - ROACHES @ MH

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

459.4 ft. - General Observation - ROACHES @ MH