- Date
- 05/12/2021
- W/O
- 891211
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00827
- PipeID
- P17025
- Time
- 10:59 PM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8951
- Sewer Name
- 22 SUNFLOWER TRUNK
- City
- SAN DIMAS
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- RFIR_WO_891211_TV22166_MAY2021
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 22 0675
- Downstream MH
- 22 0674
- Dir. of Survey
- Downstream
- Length Surveyed
- 193.7 ft.
- Total Length
- 193.7 ft.
- Structural Index
- 2
- Structural Quick
- 3B2G
- Structural Rating
- 118
- O&M Index
- 2
- O&M Quick
- 2I00
- O&M Rating
- 100
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 218
Pipe schematic from manhole 22 0675 to 22 0674 Observation photos (5)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

39.3 ft. - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

50.1 ft. - General Observation - 45% MAG COAT

120.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

145.8 ft. - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start