Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2021, 10:58 AM
  • 15 0150_H 1375_6152021_040822.mp4

Date
06/15/2021
W/O
0890821
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00635
PipeID
P26182
Time
3:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1844
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Capital Improvement Program Assesment
Project
20210615MDM_TYLER_AVENUE_RELIEF_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
15 0150
Downstream MH
H 1375
Dir. of Survey
Downstream
Length Surveyed
758.8 ft.
Total Length
758.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0150 to H 1375
MH: 15 0150MH: H 1375downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM2 ft. MGO - General Observation - 99% MAG COAT START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE202.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT386.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT546.8 ft. MGO - General Observation - 99% MAG COAT701.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT758.4 ft. MGO - General Observation - MAG COAT 99% FINISH758.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT758.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active OUT GOING LINE758.8 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (6)

  • General Observation - 99% MAG COAT START

    2 ft. - General Observation - 99% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

    202.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    386.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - 99% MAG COAT

    546.8 ft. - General Observation - 99% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

    701.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

Observations (14)

DistanceCodeObservation
546.8MGO99% MAG COAT
0MWM
0MGOConn. @ Mh, 3 O' Clock. Active
386.7SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWL
2MGO99% MAG COAT START
2SSSBLISTERING PEELING CONCRETE
758.4MGOMAG COAT 99% FINISH
0AMH4:15AM
202.8SSSBLISTERING CONCRETE UNDER MAG COAT
701.5SSSBLISTERING CONCRETE UNDER MAG COAT
758.4SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
758.8AMH4:50AM
758.4MGOConn. @ Mh, 3 O' Clock. Active OUT GOING LINE

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE UNDER 99% MAG COAT
custom_field_two
5
customer
LACSD
datetime
2021-06-15T03:58:06-07:00
documentation
MARTIN,REVELES,BARR,RAMIREZ
is_lateral_inspection
false